VS1-12 Indoor High-Voltage Vacuum Circuit Breaker – Insulating Cylinder


The VS1-12 indoor high-voltage vacuum circuit breaker with an insulated cylinder is an indoor switchgear designed for 50 Hz, 12 kV AC power systems. It serves as a protective and control unit for grid equipment and power equipment in industrial and mining enterprises. This device is suitable for frequent operations under rated working current, as well as for applications requiring multiple interruptions of short-circuit currents. Its vacuum arc extinguishing chamber is housed within an insulated sleeve, providing superior heat dissipation performance.

Product Description


Product Overview

The VS1-12 indoor high-voltage vacuum circuit breaker with an insulated cylinder is an indoor switchgear designed for 50 Hz, 12 kV AC power systems. It serves as a protective and control unit for grid equipment and power equipment in industrial and mining enterprises. This device is suitable for frequent operations under rated working current, as well as for applications requiring multiple interruptions of short-circuit currents. Its vacuum arc extinguishing chamber is housed within an insulated sleeve, providing superior heat dissipation performance.

This circuit breaker features an integrated operating mechanism and circuit breaker body design. It can be used as a fixed installation unit; by adding interlocking devices, it can meet the requirements of fixed switchgear such as XGN2 and GGIA. Alternatively, it can be equipped with a manual drawer mechanism to form a handcart unit for use in KYN28 middle‑mounted switchgear. 
The circuit breaker can be equipped with an electric chassis to meet the requirements for one‑click sequential control, making it suitable for use in unmanned, intelligent substation construction projects.

Product Model and Meaning

 

Terms of Use

1. Ambient air temperature: -15°C ~ +40°C;

2. Wind speed ≤ 35 m/s;

3. Altitude ≤ 2000 m;

4. Seismic intensity ≤ 8 degrees;

5. Environmental Humidity: Monthly average relative humidity ≤ 90%; daily average relative humidity ≤ 95%.

6. The installation location should be free from flammable, explosive, chemically corrosive substances and frequent, severe vibrations.

Note: For conditions beyond the above-mentioned normal operating environment, please consult with the manufacturer.  

Main Features

1. The VS1-12 high-voltage vacuum circuit breaker has its main components housed within an insulating cylinder made of epoxy resin via the APG molding process. This design effectively protects the vacuum arc extinguishing chamber from external factors such as mechanical impacts and environmental contamination.

2. The circuit breaker is equipped with a ceramic arc-extinguishing chamber, copper-chromium contact material, and an R‑shaped contact structure. It is characterized by strong breaking capacity, low current chopping level, and long electrical life. 3. The vacuum arc-extinguishing chamber is housed within an insulating cylinder, giving the circuit breaker maintenance‑free operation, zero pollution, no risk of explosion, low noise levels, and high insulation performance.

4. The spring‑stored‑energy operating mechanism is integrally arranged with the main body, offering high transmission efficiency and excellent operational performance. It is suitable for frequent operations and can be installed in withdrawable or fixed switchgear.

5. This vacuum circuit breaker features stable operational performance, high breaking capacity, a reasonable design, and convenient secondary wiring, making it highly suitable for power grid operation in China.

Main Technical Parameters

Serial Number

Name

Unit

Data

1

Rated Voltage

kV

12

2

1-minute power frequency withstand voltage (RMS)

kV

42

3

Rated Lightning Impulse Withstand Voltage (Peak)

kV

75

4

Rated Frequency

Hz

50

5

Rated current

A

630 1250 1600 2000 2500 3150 4000*

6

Rated short-time withstand current

kA

20 25 31.5 40 50

7

Rated Peak Withstand Current

kA

50 63 80 100 125

8

Rated short-circuit breaking current

kA

20 25 31.5 40 50

9

Rated Short-Circuit Making Current (Peak)

kA

50 63 80 100 125

10

Rated Operating Sequence

 

0-0.3s-C0-180s-C0

11

Rated short-circuit duration

S

4

12

Break time

ms

<75

13

Rated Capacitor Bank Interrupting Current

A

630/400

14

Rated Short-Circuit Breaking Current Number of Operations

Next

30

15

Mechanical life

Next

10000

16

Rated Operating Voltage

V

AC/DC 110 AC/DC 220

Ordering Instructions

Users should specify when placing an order.

a. Circuit breaker model, name, and ordered quantity;

b. The circuit breaker’s rated voltage, rated current, and rated short-circuit breaking current;

c. Rated operating voltage;

d. Names and quantities of spare parts and components;

e. If users have any other special requirements, they may specify them when placing an order.