S13 Series Fully Sealed Laminated Core Transformers


The S13 series fully sealed, stacked-core oil-immersed transformers utilize high-permeability cold‑rolled grain-oriented silicon steel sheets with a thickness of 0.23–0.3 mm for the core. They feature 45-degree full‑lapped joints and a stepped stacking method, with no punching and binding using semi‑dry, non‑woven glass fiber tape, effectively reducing no‑load losses and operating noise.

Product Description


Product Overview

The S13 series fully sealed, stacked-core oil-immersed transformers utilize high-permeability cold‑rolled grain-oriented silicon steel sheets with a thickness of 0.23–0.3 mm for the core. They feature 45-degree fully skewed joints and a stepped stacking method, with no punching and binding using semi‑dry, non‑woven glass fiber tape, effectively reducing no‑load losses and operating noise.

Product Model and Meaning

 

Terms of Use

1. Altitude ≤ 1000 m;

2. Ambient air temperature: -25°C to +45°C, with an average temperature of ≤+30°C during the hottest month.

3. Environmental Humidity: Monthly average relative humidity ≤ 90%; daily average relative humidity ≤ 95%.

4. Pollution Level: Level. 
Main Features

1. The iron core is made of high-permeability cold‑rolled grain‑oriented silicon steel sheets, which reduces operating losses.

2. The coils are wound with high‑quality QQ polyacetal enameled round copper wire and flat copper wire drawn from oxygen‑free copper rods, offering sufficient electrical strength, mechanical strength, and heat dissipation capability.

3. The fuel tank is welded from high‑quality cold‑rolled steel sheet. After acid pickling and phosphating both inside and outside the tank, it undergoes a three‑coat primer‑topcoat painting process, offering excellent corrosion resistance while maintaining a sleek and elegant appearance.

Main Technical Parameters

Capacity

Voltage Ratio and Tap Range

Connection 
Group

No-load loss 
(W)

No-load current 
(%)

Load Loss (W)

Impedance Voltage 
(%)

High Voltage (kV)

High-voltage tap range

Low Voltage (kV)

D connect

Y connection

30 

6
6.3

10
10.5
11

±2 × 2.5% 
±5%

0.4 

Dyn11
Yyn0

80 

1.50 

630 

600 

50 

100 

1.30 

910 

870 

63 

110 

1.20 

1090 

1040 

80 

130 

1.20 

1310 

1250 

100 

150 

1.10 

1580 

1500 

125 

170 

1.10 

1890 

1800 

160 

200 

1.00 

2310 

2200 

200 

240 

1.00 

2730 

2600 

250 

290 

0.90 

3200 

3050 

315 

340 

0.90 

3830 

3650 

400 

410 

0.80 

4520 

4300 

500 

480 

0.80 

5410 

5150 

630 

570 

0.60 

6200 

6200 

4.5 

800 

700 

0.60 

7500 

7500 

1000 

830 

0.60 

10300 

10300 

1250 

970 

0.50 

12000 

12000 

1600 1170 0.50 14500 14500 

Ordering Instructions

1. Product model, voltage level, tap range, and connection group;

2. Order quantity and installation altitude;

3. Special requirements from users regarding electrical appliances, such as the color and material of the enclosure, installation method, and protection rating.


Keywords:

S13 Series Fully Sealed Laminated Core Transformers

Online Quotation Request

* Note: Please ensure that you fill in the information accurately and keep communication open. We will contact you as soon as possible!

Submit

More products