S13-M·RL Series Three-Dimensional Rolled Core Transformer


The S13-M·RL series of three-dimensional core oil-immersed transformers breaks away from the traditional planar design and adopts a three-phase symmetrical three-dimensional structure. The magnetic circuits of the transformer’s three-phase cores are perfectly symmetrical, significantly reducing magnetic reluctance and leading to a marked decrease in excitation current and no-load losses. The core is fully solidified into a single unit, greatly enhancing its mechanical strength and seismic resistance, while also lowering operating noise and resulting in a more compact structure. With numerous advantages such as energy efficiency, environmental friendliness, stable and reliable performance, and anti-theft features, these transformers are fully aligned with China’s national energy conservation policies.

Product Description


Product Overview

The S13-M·RL series of three-dimensional core oil-immersed transformers breaks away from the traditional planar design and adopts a three-phase symmetrical three-dimensional structure. The magnetic circuits of the transformer’s three-phase cores are perfectly symmetrical, significantly reducing magnetic reluctance and leading to a marked decrease in excitation current and no-load losses. The core is fully solidified into a single unit, greatly enhancing its mechanical strength and seismic resistance, while also lowering operating noise and resulting in a more compact structure. With numerous advantages—including energy efficiency, environmental friendliness, stable and reliable performance, and anti-theft features—the transformers fully align with China’s national energy conservation policies.

Product Model and Meaning

 

Terms of Use

1. Altitude ≤ 1000 m;

2. Ambient air temperature: -25°C to +45°C, with an average temperature of ≤+30°C during the hottest month.

3. Environmental Humidity: Monthly average relative humidity ≤ 90%; daily average relative humidity ≤ 95%.

4. Pollution Level: Level. 
Main Features

1. The core adopts a three‑phase symmetrical three‑dimensional structure. The layered, three‑dimensional wound core features no interlayer joints, ensuring uniform magnetic flux distribution throughout the magnetic circuit with no prominent high‑resistance zones. There is no distortion in magnetic flux density at joint locations, and the direction of magnetic flux is perfectly aligned with the crystal orientation of the silicon steel laminations. Moreover, the lengths of the three‑phase magnetic circuits are exactly equal, resulting in complete symmetry across all three phases and highly balanced no‑load currents for the three phases. Thanks to the use of this specialized three‑dimensional structure, the amount of material used in the yoke portion of the core is reduced by 25% compared to traditional laminated cores, while the angular weight is also decreased—accounting for roughly 6% of the total core weight—thereby lightening the overall weight of the core.

2. Because the iron core has no joints, it experiences minimal vibration and generates very little noise.

3. The coil is wound directly onto the iron core, which not only enhances the coil’s strength but also improves its anti-theft performance.

4. The structure is compact and occupies a small footprint; the unique three-dimensional core design ensures a tightly packed, rationally arranged product configuration. The planar footprint of the transformer body is reduced by 10–15% compared to conventional products, while the overall height is lowered by 10–20%. When installed in a packaged substation, the volume of the substation can be reduced by nearly one quarter.

Main Technical Parameters

Performance Parameters of S13 Fully Sealed Three-Dimensional Rolled Core Transformers

Capacity

Voltage Ratio and Tap Range

Connection  
Group

No-load loss  
(W)

No-load current  
(%)

Load Loss (W)

Impedance Voltage  
(%)

High Voltage (kV)

High-voltage tap range

Low Voltage (kV)

D connect

Y connection

30 


6.3 

10 
10.5 
11

±2×2.5% 
±5%

0.4 

Dyn11 
Yyn0

80 

1.50 

630 

600 

50 

100 

1.30 

910 

870 

63 

110 

1.20 

1090 

1040 

80 

130 

1.20 

1310 

1250 

100 

150 

1.10 

1580 

1500 

125 

170 

1.10 

1890 

1800 

160 

200 

1.00 

2310 

2200 

200 

240 

1.00 

2730 

2600 

250 

290 

0.90 

3200 

3050 

315 

340 

0.90 

3830 

3650 

400 

410 

0.80 

4520 

4300 

500 

480 

0.80 

5410 

5150 

630 

570 

0.60 

6200 

6200 

4.5 

800 

700 

0.60 

7500 

7500 

1000 

830 

0.60 

10300 

10300 

1250 

970 

0.50 

12000 

12000 

1600 1170 0.50 14500 14500 

Ordering Instructions

1. Product model, voltage level, tap range, and connection group;

2. Order quantity and installation altitude;

3. Special requirements from users regarding electrical appliances, such as the color and material of the enclosure, installation method, and protection rating.


Keywords:

S13-M·RL Series Three-Dimensional Rolled Core Transformer

Online Quotation Request

* Note: Please ensure that you fill in the information accurately and keep communication open. We will contact you as soon as possible!

Submit