GGD Low-Voltage Fixed Switchgear


The GGD low-voltage fixed switchgear is suitable for power users such as power plants, substations, and industrial and mining enterprises, serving as a distribution system for AC 50 Hz with a rated operating voltage of 400 V and a rated current up to 3150 A. It is used for the conversion, distribution, and control of electrical energy in power, lighting, and distribution equipment. The product features flexible circuit configurations, strong practicality, and a novel structural design. It is one of the alternative products to China’s assembled, fixed-panel switchgear cabinets.

Product Description


Product Overview

The GGD low-voltage fixed switchgear is suitable for power users such as power plants, substations, and industrial and mining enterprises, serving as a distribution system for AC 50 Hz with a rated operating voltage of 400 V and a rated current up to 3150 A. It is used for the conversion, distribution, and control of electrical energy in power, lighting, and distribution equipment. The product features flexible circuit configurations, strong practicality, and a novel structural design. It is one of the alternative products to China’s assembled, fixed-panel switchgear cabinets.

Product Model and Meaning

 

Operating Environment

1. Ambient air temperature: -5°C to +40°C, with an average temperature of ≤+35°C over a 24-hour period.

2. For indoor installation and use, the altitude of the installation location must be ≤ 2000 m.

3. Air cleanliness: At a high temperature of +40°C, the relative humidity should be ≤50%; at lower temperatures, a higher relative humidity is permissible. For example, at +20°C, the relative humidity may reach 90%, but considering temperature fluctuations, moderate condensation may occasionally occur.

4. During installation, the tilt angle relative to the vertical plane should be ≤5°.

5. The equipment should be installed in locations free from severe vibration and impact, as well as in environments where electrical components are not exposed to corrosive conditions. Note: If the operating environment exceeds the above‑mentioned standard conditions, consultation with the manufacturer is required. 
 

Main Features

The cabinet body adopts a standard cabinet design, with the frame constructed by partially welding together cold‑formed 8MF steel profiles. The cabinet’s components are designed according to modular principles and feature mounting holes spaced at 20‑mm increments, resulting in a highly versatile system that can be interconnected to form various frame structures and units tailored to meet specific requirements. The top and bottom ends of the cabinet are equipped with varying numbers of heat dissipation slots, creating a natural airflow path from bottom to top within the cabinet to achieve effective cooling.

The cabinet doors are connected to the frame using pivot-style hinges, making installation and removal convenient. Each edge of the door is fitted with a U-shaped rubber strip; when the door is closed, the strip compresses against the frame, preventing direct impact between the door frame and the cabinet body while also enhancing the door’s level of protection. The instrument doors housing electrical components are connected to the frame via multi-strand flexible copper wire, and the mounting components inside the cabinet are secured to the frame using knurled screws, thereby forming a complete grounding protection circuit throughout the entire cabinet.

The main busbar is located at the middle to rear of the top of the cabinet and is secured using ZMJ busbar clamps. The ZMJ features a modular, block‑like structure that is manufactured via high‑temperature injection molding with flame‑retardant materials, offering high mechanical strength and excellent insulation performance. When necessary, the cabinet’s top panel can be removed for convenient on-site assembly and adjustment of the main busbar. Lifting rings are installed at the four corners of the cabinet top for hoisting and transportation.

Main Technical Parameters

Parameter Name

Unit

Parameters

Rated Insulation Voltage

V

AC660

Rated operating voltage

V

AC380

Rated Impulse Withstand Voltage

V

AC2500

Rated Frequency

Hz

50

Main busbar operating current

A

3150

Rated Peak Withstand Current (0.1 s)

kA

Up to 105

Rated short-time withstand current (1 min)

kA

Up to 50

Protection Level

 

IP30

Cabinet external dimensions: Width × Depth × Height (mm)

mm

600/800/1000 × 600/800/1000 × 2200

Ordering Instructions

1. Main Circuit System Diagram;

2. Auxiliary Circuit Electrical Schematic;

3. List of Components Inside the Cabinet (including component model, name, specifications, and quantity);

4. Layout drawing of switchgear;

5. Cabinet color (unless otherwise specified, products will be supplied according to the company’s standard);

6. List of Required Spare Parts and Components;

7. Other Terms of Use


Keywords:

GGD Low-Voltage Fixed Switchgear

Online Quotation Request

* Note: Please ensure that you fill in the information accurately and keep communication open. We will contact you as soon as possible!

Submit